Environmentally friendly
No use of sea water, no thermal discharge, no effect to the sea water components.
High security because of dry-type
Since no water is used, there is no danger of electric shock or electrical leakage ,so testing on ships is possible.
Labor-saving and simple operation
Combined structure of a resistance unit and a control device for easy transfer and installation, as well as all weather testing is possible.
Container-type for all weather
No adjustment is needed, so short tests by one person are possible. Interactive-type touch panel for easy operation is used.
※It is possible to rent other models than RESI-MASTER 2400L. Please inquire for details.
6600V 2000kVA generator testing is possible by renting the dry-type generator load test machine RESI-MASTER 2400L!
For the generator load test machine rental service we offer 1~5 in the above diagram, as well as cables for the machines and grounding wires.
Rental Machine Set Details | |
---|---|
①Power Panel | Outdoor model cubicle type Standard Machine ・DS, VCB ・Voltmeter, Ammeter ・LBS w/incoming current control capability Protective capability ・Earth-fault relay ・Overcurrent relay ・Transformer temperature abnormality detector Dimensions:W1,780×D2,300×H2,440 Weight:1,440kg |
②Transformer Panel | Outdoor model Use with transformer ・Primary voltage: 6600V, Secondary voltage: 450V ・2000kVA Dimensions:W3,000×D2,480×H2,550 Weight:6,860kg |
③RESI-MASTER2400L | Outdoor model container type ・Testing max capacity = 2000kW Power Factor 1 ・Testing min capacity = 1kW Power Factor 1 ・Testing voltage = 450V 50/60Hz |
④Remote Control Panel w/Touchscreen | ・Control power panels and RESI-MASTER2400L with just one touchscreen ・Touchscreen weight = appr. 1kg ・Weight: 1kg+ Dimensions:W224×D99×H180 Weight:Less than 1kg |
⑤Control Generator | Diesel generator:3φ AC220V 60Hz 25kVA Dimensions:W700×D1,500×H1,000 Weight:705kg |
Type | RESI-MASTER200L | RESI-MASTER1000L | RESI-MASTER2000L | RESI-MASTER4000L |
---|---|---|---|---|
Maximum capacity | 200kW | 1000kW | 2000kW | 4000kW |
Minimum capacity | 1kW | 1kW | 1kW | 1kW |
Power Factor | 1.0 | 1.0 | 1.0 | 1.0 |
Test Power Supply | 3φ 450V 50/60Hz | 3φ 450V 50/60Hz | 3φ 450V 50/60Hz | 3φ 450V 50/60Hz |
Maximum current value | 260A | 1285A | 2566A | 5135A |
Control power source | 3φ 200/220V 50/60Hz | 3φ 200/220V 50/60Hz | 3φ 200/220V 50/60Hz | 3φ 200/220V 50/60Hz |
Paint color | 7.5YR 7.5/16 | 7.5YR 7.5/16 | 7.5YR 7.5/16 | 7.5YR 7.5/16 |
Dimensions(Not including the protruding part) | W:1,100×D:1,655×H:2,260 | W:1,500×D:3,500×H:2,750 | W:2,300×D:6,058×H:2,586 | W:2,432×D:6,058×H:2,860 |
Weight | 1,000kg | 3,500kg | 7,000kg | 9,500kg |
Block diagram | DOWNLOAD | DOWNLOAD | DOWNLOAD | DOWNLOAD |
Outline (Diagram) | DOWNLOAD | DOWNLOAD | DOWNLOAD | DOWNLOAD |
Type | RESI-MASTER2000H | RESI-MASTER4000H | REACTOR 2000H |
---|---|---|---|
Maximum capacity | 2000kW | 4000kW | 2000kVar |
Minimum capacity | 10kW | 10kW | 10kVar |
Power Factor | 1.0 | 1.0 | - |
Test Power Supply | 3φ 6600V 50/60Hz | 3φ 6600V 50/60Hz | 3φ 6600V 50/60Hz |
Maximum current value | 175A | 350A | 175A |
Control power source | 3φ 200/220V 50/60Hz | 3φ 200/220V 50/60Hz | 3φ 200/220V 50/60Hz |
Paint color | 7.5YR 7.5/16 | 7.5YR 7.5/16 | 7.5YR 7.5/16 |
Dimensions(Not including the protruding part) | W:2,400×D:4,200×H:2,800 | W:2,400×D:6,700×H:2,800 | W:2,400×D:6,700×H:2,800 |
Weight | 5,000kg | 9,500kg | 14,000kg |
Disconnection detection capability (※1) | ○ | ○ | - |
Block diagram | DOWNLOAD | DOWNLOAD | DOWNLOAD |
Outline (Diagram) | DOWNLOAD | DOWNLOAD | DOWNLOAD |
※We are able to produce other than listed above for both Low and High. Please inquire for details.
Please inquire from the following telephone number or inquiry form,to our company.
I will contact you at a later date than the person in charge.